SP-MBUS-40V-IP


Combined coarse and fine surge protection for M-Bus networks

Application

The surge protection is designed to protect a two wire communication line of an M-Bus network against impulse overvoltage. The two stage protection protects M-Bus devices against overvoltage between the wires and between the ground and each wire. The surge protection is suitable for M-Bus slave and master devices regardless of type.

The protection has a separate lightning arrester for connection to the communication cable shielding. This can be used for prevention of reverse currents between separate ground points or grounding circuits.

Main characteristics

  • Wall mounted, ingress protection IP54.
  • Suitable for protection of slave and also master devices.
  • Maximum current load 0.4A – 255 M-Bus devices.
  • Maximum M-Bus operating voltage 44V.
  • Peak surge current In(8/20μs) 10kA.
  • Serial resistance per line 2.2 Ω.
  • Lightning arrester protection for cable shielding.
  • Plastic box with dimensions of 100x100x39mm.

Guarantee of quality

  • In order to achieve maximum possible level of reliability and quality the devices are electrically tested and pass visual inspection during manufacturing.
Electrical properties
Operating voltage A-B 40V
Maximum operating voltage A-B 44V
Maximum operating current A,B 0.4A – 255 M-Bus slaves
Maximum operating voltage A,B to PG 90V
Peak surge current In (8 / 20 μs) 10 kA
Response time < 1ns
Maximum clamping voltage A-B at In < 74V
Maximum clamping voltage A,B to ground at In < 300V
Serial resistance per line 2.2 Ω
Connector terminals for wires of up to 2.5 mm² cross-section area, 4mm² for PE (Grounding wire)
Temperature
Operating range -40°C to 80°C
Mechanical construction
Mechanical design plastic box
Mounting two holes spread 110mm apart
Dimensions: height x width x depth 100 x 100 x 39 mm (100 x 120 x 39 mm with tabs)
Protection classification IP54
Weight 93g

End user

Price list for individuals and companies which do not buy converters for resale.

Pricelist

Integrator

Price list for companies which buy converters for the purpose of resale to their custommers as manufacturers or suppliers.

Pricelist (registered business partners)

The price list is available only to registered business partners.
Registration request.

Registration

Manuals

Name / File
Date
Size
Manual
Surge_Protection_MBUS-40V-IP_v1_2_EN_manual.pdf
Date:
26.6. 2016
Size:
1.78 MB

Inside view

back ↑

Typical application

Recommended wiring option 1

Recommended wiring option 2

back ↑

Connectors

Connectors Type
Protected M-Bus
A, B
Terminals for connecting the surge protected M-Bus line. Connection to the protected M-Bus device. Terminals wire max. 2.5mm²
M-Bus input
A, B
Terminals for connecting the M-Bus line with the risk of overvoltage occurrence. Terminals wire max. 2.5mm²
PE
Grounding terminal. Connect to the grounding of the electrical installation. Use shortest possible wire with cross-section of 2.5 to 4 mm² Terminals wire max. 4mm²
Cable shield Terminal for connecting the cable shielding. Terminals wire max. 2.5mm²

back ↑

Dimensions