RS485toMBus-5M

M-Port line

RS485 to M-Bus communication converter

Application

Remote data retrieval from M-Bus devices via the RS485 serial communication line in industry and building automation. The most frequently used M-Bus slave devices are heat, water and electricity consumption meters.

Description

The RS485toMBus-5M converter provides a RS485 to M-Bus interface conversion. There is no change in the content of the messages or communication speed during the conversion. The maximum possible number of M-Bus slave devices that can be connected is five.

Main characteristics

M-Bus port
  • Connection of 1 to 5 M-Bus slave devices.
  • Surge protection guaranteeing superior durability against overvoltage.
  • Current protection against overload and short circuit on the communication line with LED status indication.
Power supply
  • Wide range of power supply voltages. DC 7.5 – 40V and AC 7.5 – 28V.
  • Overvoltage protection.
  • LED power supply indication.
RS485
  • Signals: A, B and GND.
  • Protections against overvoltage.
  • Galvanic separation from the M-Bus line.
Mechanical construction
  • Plastic box with mounting on 35 mm DIN rail.
  • Narrow box. 17.5mm mounting width on the DIN rail.

Differences from the RS485toMBus-5 converter

  • Very small mounting width on the DIN rail.
  • Less powerful overvoltage protection on the M-Bus line.
  • Less powerful M-Bus line driver. The maximum length of the M-Bus line is in the range of hundreds of meters.
  • Smaller operating temperature range.

Guarantee of quality

  • Each converter passes through several functional electrical tests during the production. Additionally a communication test is performed after final assembly.
  • EMC certification in an accredited laboratory for industrial environment.
  • Solid design and construction based on many years practical experience.
RS485 communication interface
Communication signals A (+ Tx/Rx), B (- Tx/Rx), GND
Protection overvoltage protection TVS 600W
Terminating resistors A 10kΩ to +5V, B 10kΩ to GND
Galvanic separation 1kV from M-Bus line
Connector terminal block with plug-in connector for wires of up to 2.5 mm² cross-section area
M-Bus Master communication interface
Number of devices that can be connected 1 to 5 SLAVE devices, idle current max. 7.5mA
Baud rate 300 – 9600 bps
Protection – overvoltage protection TVS 600W
– electronic protection against overloads and short circuit on the communication line
note: converter can withstand sustained short circuit on the communication line
Galvanic separation 1kV from power supply and from RS485 line
Connector terminal block with plug-in connector for wires of up to 2.5 mm² cross-section area
Power supply
Recommended range of power supply voltages
DC power supply 7.5V to 40V
AC power supply 7.5V to 28V
Protection – overvoltage protection TVS 1500W
Power consumption 0.25W to 1.1W. Depends on M-Bus line load and power supply.
Maximum power consumption during a short on the M-Bus line is 1.5W.
Connector terminal block with plug-in connector for wires of up to 2.5 mm² cross-section area
Status LEDs
Power – blue indication of connected supply voltage
Transmit – green indication of data broadcasting on the M-Bus line
Receive – yellow indication of data reception on the M-Bus line
Overload/Short – red indication of M-Bus line overload – flashing (idle current > 7.5mA)
indication of short on the M-Bus line – turned on (resistance of the line < 500Ω)
Temperature
Operating range -20°C to 70°C
Mechanical construction
Mechanical design plastic box
Mounting 35 mm DIN rail (EN 50022 top hat rail)
Dimensions: height x width x length 56.5 x 17.5 x 97.5 mm
Protection classification IP20
Weight 52g

EMC compatibility of the M-Bus converter has been tested according to the following home environment standards.

EMC emission tests
Standard Test Level
EN 55022 Power line – CONDUCTED EMISSIONS 10/150 kHz – 30 MHz Class B
EN 55022 RADIATED EMISSIONS (Electric Field) 30 MHz – 1000 MHz Class B
EMC immunity tests
Standard Test Level
EN 61000-4-2 ELECTROSTATIC DISCHARGE (ESD) – Contact discharge ± 4 kV
EN 61000-4-2 ELECTROSTATIC DISCHARGE (ESD) – Air discharge ± 8 kV
EN 61000-4-4 ELECTRICAL FAST TRANSIENT/BURST – Power line ± 4 kV
EN 61000-4-4 ELECTRICAL FAST TRANSIENT/BURST – M-Bus line ± 4 kV
EN 61000-4-5 SURGE IMMUNITY – Power line. Common/differential mode. ± 1 kV / ± 0.5 kV
EN 61000-4-5 SURGE IMMUNITY – M-Bus line. Cable shielding. ± 4 kV
EN 61000-4-5 SURGE IMMUNITY – M-Bus line. Common/differential mode.* ± 2 kV / ± 1 kV
EN 61000-4-6 CONDUCTED DISTURBANCES, INDUCED BY RADIO-FREQUENCY FIELDS 0.15MHz – 80 MHZ. Power line and M-Bus line. 3 V

* test carried out at the request of the manufacturer. The M-Bus port has an increased durability against overvoltage. Carrying out this type of test is not required with the use of shielded cable.

End user

Price list for individuals and companies which do not buy converters for resale.

Pricelist

Integrator

Price list for companies which buy converters for the purpose of resale to their custommers as manufacturers or suppliers.

Pricelist (registered business partners)

The price list is available only to registered business partners.
Registration request.

Registration

Leaflet

Name / File
Date
Size
Promotional leaflet
RS485toMBus-5M_flyer_v1_0_EN.pdf
Date:
22.11. 2021
Size:
276 kB

Manuals

Name / File
Date
Size
Manual
RS485toMBus-5M_manual_v1_0_EN.pdf
Date:
22.11. 2021
Size:
1.06 MB

Top view

back ↑

Typical application

Typical wiring of the converter with M-Bus devices, power supply and a RS485 serial communication link connection to a computer. 

back ↑

LED indication

Status LEDs Color
Power Indication of connected supply voltage. blue
Transmit Indication of data transmission on the M-Bus line. green
Receive Indication of data reception on the M-Bus line. yellow
Overload/Short Indication of short and overload on the M-Bus line. red
– indication of a short on the M-Bus line (resistance of line < 500 Ω) – LED turned on
– indication of M-Bus line overload – alternating flashing of Overload/Short LED and Receive LED

back ↑

Connectors on the Power Supply and M-Bus side

Connector Type
M-Bus Connector for the M-Bus line. built-in
Power Connector for power supply. built-in

back ↑

Connectors on the RS485 side

Connectors Type
RS485 Connector for the RS485 interface. built-in

back ↑

Dimensions