Communication signals | A (+ Tx/Rx), B (- Tx/Rx), GND |
Protection | overvoltage protection TVS 600W |
Terminating resistors | A 1kΩ to +5V, B 1kΩ to GND, between A & B 120Ω - JUMPER |
Galvanic separation | 1kV from M-Bus line |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Number of devices that can be connected | 1 to 4 SLAVE devices, idle current max. 6 mA |
Baud rate | 300 - 9600 bps |
Protection | - overvoltage protection TVS 600W |
- electronic protection against overloads and short circuit on the communication line |
note: converter can withstand sustained short circuit on the communication line |
Galvanic separation | 1kV from power supply and from RS485 line |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Recommended range of power supply voltages |
DC power supply | 7V to 28V |
Maximum limits of supply voltage - permanent operation at these voltages is not recommended |
Minimum DC power | 6.5V - minimal voltage necessary for the operation of the converter |
Maximum DC power | 30V - above this the overvoltage protection will activate |
Protection | - overvoltage protection TVS 600W |
Power consumption | 0.3W to 1W. Depends on M-Bus line load and power supply. |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Power - green | indication of connected supply voltage |
Transmit - green | indication of data broadcasting on the M-Bus line |
Receive - yellow | indication of data reception on the M-Bus line |
Overload/Short - red | indication of M-Bus line overload – flashing (idle current > 8mA) |
indication of short on the M-Bus line – turned on (resistance of the line < 500Ω) |
Operating range | -20°C to 70°C |
Mechanical design | plastic box |
Mounting | 35 mm DIN rail (EN 50022 top hat rail) |
Dimensions: height x width x length | 58 x 36 x 95 mm |
Protection classification | IP20 |
Weight | 70g |
EMC compatibility of the M-Bus converter has been tested according to the following industrial environment standards.
Standard | Test | Level |
EN 55011 | Power line - CONDUCTED EMISSIONS 10/150 kHz - 30 MHz | Class A |
EN 55011 | RADIATED EMISSIONS (Electric Field) 30 MHz - 1000 MHz | Class A |
|
Standard | Test | Level |
EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Contact discharge | ± 4 kV |
EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Air discharge | ± 8 kV |
EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - Power line | ± 4 kV |
EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - M-Bus, RS485 line | ± 4 kV |
EN 61000-4-5 | SURGE IMMUNITY - Power line. Common/differential mode. | ± 1 kV / ± 0.5 kV |
EN 61000-4-5 | SURGE IMMUNITY - M-Bus, RS485 line. Cable shielding. | ± 4 kV |
EN 61000-4-5 | SURGE IMMUNITY - M-Bus line. Common/differential mode.* | ± 2 kV / ± 1 kV |
EN 61000-4-6 | CONDUCTED DISTURBANCES, INDUCED BY RADIO-FREQUENCY | 10 V |
FIELDS 0.15MHz - 80 MHZ. Power line and M-Bus line. |
* test carried out at the request of the manufacturer.
The M-Bus port has an increased durability against overvoltage. Carrying out this type of test is not required with the use of shield cable.